The feeder conductors to the fire pump are 1 awg copper with thwn insulation in 1 25 inch rigid metal conduit and liquid tight flexible metal conduit.
Fire pump motor overcurrent protection sizing.
See example 3 to size a transformer.
I did the wiring for a 75 horsepower 480 volt three phase fire pump motor with a nameplate full load current rating of 94 amperes.
If you install overcurrent protection devices ahead of the feeder pump circuits in the power supply for either utility or customer owned supply systems these protective devices shall be capable of carrying the locked rotor current of the fire pump motor s and the pressure maintenance pump motor s and associated fire pump accessory equipment.
The overcurrent protection complies with the earlier requirements in that it is intended only for short circuit fault protection and is set.
It must be sized for 125 of the fire pump motors and jockey pump and 100 of the remaining loads.
If a transformer supplies an electric fire pump motor size it at least 125 of the sum of the fire pump and pressure maintenance pump s motor loads and 100 of the ampere rating of the fire pump s accessory equipment 695 5 a.
You cannot provide secondary overcurrent protection.
To size its ocpd we size it based on the locked rotor current of the fire pump per nec 695 4 b 1.
So for a 250hp fire pump motor its ocpd rating would be 2000a.
To size its conductor ampacity we calculate it as 1 25 times the fire pump fla 302a x 1 25 377a 400a ampacity.